{"id":14109,"date":"2026-07-20T12:12:30","date_gmt":"2026-07-20T10:12:30","guid":{"rendered":"https:\/\/help.fetura.pl\/knowledge-base\/configuring-alarms-on-farmwatch-pro-digital-inputs-via-fetura-cloud\/"},"modified":"2026-07-22T16:22:34","modified_gmt":"2026-07-22T14:22:34","slug":"configuring-alarms-on-farmwatch-pro-digital-inputs-via-fetura-cloud","status":"publish","type":"ht_kb","link":"https:\/\/help.fetura.pl\/en\/knowledge-base\/configuring-alarms-on-farmwatch-pro-digital-inputs-via-fetura-cloud\/","title":{"rendered":"Configuring Alarms on FarmWatch Pro Digital Inputs via Fetura CLOUD"},"content":{"rendered":"\n<p class=\"wp-block-paragraph\">This article will guide you step by step through the process of configuring alarms for digital inputs in the FarmWatch Pro system using the Fetura CLOUD platform.<\/p>\n\n\n\n<p class=\"wp-block-ht-blocks-messages wp-block-hb-message wp-block-hb-message--withicon is-style-alert\"><strong>NOTE<\/strong><br>Before you begin configuring alarms, make sure that the digital inputs have been properly connected and configured on the FarmWatch Pro device.<br>If you haven\u2019t already, refer to the article describing how to connect and configure the digital inputs. <a href=\"https:\/\/help.fetura.pl\/en\/knowledge-base\/connecting-and-configuring-digital-inputs-for-farmwatch-pro\/\" data-type=\"link\" data-id=\"https:\/\/help.fetura.pl\/knowledge-base\/podlaczenie-i-konfiguracja-wejsc-cyfrowych-dla-farmwatch-pro\/\">Click here!<\/a><\/p>\n\n\n\n<h2 class=\"wp-block-heading\">1. Preview<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">To view the digital inputs, go to the <strong>Dashboard<\/strong> section (highlighted in red). Next, click the three-dot icon in the top bar (highlighted in blue) and select the <strong>Digital Inputs<\/strong> option (highlighted in green). <\/p>\n\n\n\n<figure class=\"wp-block-image aligncenter size-large\"><img decoding=\"async\" width=\"1024\" height=\"353\" src=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/Puplit-eng-1-1024x353.png\" alt=\"A screenshot of the main panel on the Fetura CLOUD platform. The screenshot highlights the icon labeled &quot;Dashboard&quot; on the side navigation bar. In the &quot;Dashboard&quot; section, there is a horizontal navigation bar with three dots highlighted, which display the remaining tabs. Among the remaining tabs, the &quot;DIGITAL INPUTS&quot; tab is highlighted.   \" class=\"wp-image-14395\" srcset=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/Puplit-eng-1-1024x353.png 1024w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/Puplit-eng-1-300x103.png 300w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/Puplit-eng-1-768x265.png 768w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/Puplit-eng-1-50x17.png 50w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/Puplit-eng-1-1536x530.png 1536w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/Puplit-eng-1-60x21.png 60w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/Puplit-eng-1-100x34.png 100w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/Puplit-eng-1.png 1897w\" sizes=\"(max-width: 1024px) 100vw, 1024px\" \/><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\">When you open the panel, you&#8217;ll see a list of digital inputs. The inputs not assigned to a specific room or building are displayed first, followed by the inputs that have already been assigned. <\/p>\n\n\n\n<p class=\"wp-block-ht-blocks-messages wp-block-hb-message wp-block-hb-message--withicon is-style-info\">We have already covered how to assign inputs and sensors on the Fetura CLOUD platform in the article &#8220;How to Add a Sensor to a Building?&#8221;  <a href=\"https:\/\/help.fetura.pl\/en\/knowledge-base\/how-do-i-add-a-sensor-to-a-building\/\" data-type=\"link\" data-id=\"https:\/\/help.fetura.pl\/knowledge-base\/jak-dodac-czujnik-do-budynku\/\">Click here!<\/a>  To go to the article.<\/p>\n\n\n\n<figure class=\"wp-block-image aligncenter size-large\"><img decoding=\"async\" width=\"1024\" height=\"653\" src=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-1-1024x653.png\" alt=\"Screenshot of the &quot;DIGITAL INPUTS&quot; tab on the Fetura CLOUD platform. The screenshot shows:\nAt the top\u2014the navigation bar,\nIn the middle\u2014digital input management panels (three are visible),\nAt the bottom\u2014information about the number of selected input panels and three dots. \" class=\"wp-image-14396\" srcset=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-1-1024x653.png 1024w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-1-300x191.png 300w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-1-768x490.png 768w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-1-50x32.png 50w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-1-60x38.png 60w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-1-100x64.png 100w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-1.png 1534w\" sizes=\"(max-width: 1024px) 100vw, 1024px\" \/><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\">To access the settings for the selected input, click it in the list (highlighted in blue). Once you select an input, the information bar (highlighted in red) will display the number of selected items. <\/p>\n\n\n\n<figure class=\"wp-block-image aligncenter size-large\"><img decoding=\"async\" width=\"1024\" height=\"562\" src=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-2-1024x562.png\" alt=\"Screenshot of the &quot;DIGITAL INPUTS&quot; tab on the Fetura CLOUD platform. The screenshot shows the IN1 input panel highlighted; when selected, the three dots change color from gray to blue, indicating that the option is available. \" class=\"wp-image-14397\" srcset=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-2-1024x562.png 1024w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-2-300x165.png 300w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-2-768x422.png 768w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-2-50x27.png 50w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-2-60x33.png 60w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-2-100x55.png 100w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-2.png 1532w\" sizes=\"(max-width: 1024px) 100vw, 1024px\" \/><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\">Next to the information bar is an icon with three dots. Clicking it will display a list of available options for the selected input (highlighted in red). <\/p>\n\n\n\n<figure class=\"wp-block-image aligncenter size-large\"><img decoding=\"async\" width=\"1024\" height=\"556\" src=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-3-1024x556.png\" alt=\"Screenshot of the &quot;DIGITAL INPUTS&quot; tab on the Fetura CLOUD platform. The screenshot shows the tabs displayed after clicking the three dots; the available settings are:\nAlarm Configuration,\nArm Alarm,\nDisarm Alarm,\nSchedule,\nClear Alarms (grayed out). \" class=\"wp-image-14398\" srcset=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-3-1024x556.png 1024w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-3-300x163.png 300w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-3-768x417.png 768w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-3-50x27.png 50w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-3-1536x834.png 1536w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-3-60x33.png 60w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-3-100x54.png 100w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-3.png 1559w\" sizes=\"(max-width: 1024px) 100vw, 1024px\" \/><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\">You can check the current status of the entry by hovering your cursor over the gear icon (highlighted in red).<\/p>\n\n\n\n<figure class=\"wp-block-image aligncenter size-large\"><img decoding=\"async\" width=\"1024\" height=\"197\" src=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-4-1024x197.png\" alt=\"A screenshot of the &quot;DIGITAL INPUTS&quot; tab on the Fetura CLOUD platform. The screenshot shows the IN1 input panel with the cursor hovering over the gear icon, which displays a small input status panel. \" class=\"wp-image-14400\" srcset=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-4-1024x197.png 1024w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-4-300x58.png 300w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-4-768x148.png 768w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-4-50x10.png 50w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-4-1536x295.png 1536w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-4-60x12.png 60w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-4-100x19.png 100w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/DIG-4.png 1544w\" sizes=\"(max-width: 1024px) 100vw, 1024px\" \/><\/figure>\n\n\n\n<h2 class=\"wp-block-heading\">2. Arming\/Disarming the Alarm<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">To arm the alarm, go to the input settings and select the <strong>ARM ALARM<\/strong> option (highlighted in blue).<\/p>\n\n\n\n<figure class=\"wp-block-image aligncenter size-large\"><img decoding=\"async\" width=\"1024\" height=\"524\" src=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/ARM-1-1024x524.png\" alt=\"Screenshot of the &quot;DIGITAL INPUTS&quot; tab on the Fetura CLOUD platform. The screenshot shows the digital input panels, with the tabs visible after clicking the three dots. The &quot;Arm Alarm&quot; option is selected.  \" class=\"wp-image-14401\" srcset=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/ARM-1-1024x524.png 1024w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/ARM-1-300x154.png 300w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/ARM-1-768x393.png 768w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/ARM-1-50x26.png 50w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/ARM-1-1536x786.png 1536w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/ARM-1-60x31.png 60w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/ARM-1-100x51.png 100w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/ARM-1.png 1543w\" sizes=\"(max-width: 1024px) 100vw, 1024px\" \/><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\">The system will ask you to confirm the operation. To continue, click <strong>ARM ALARM<\/strong> (highlighted in blue) again. <\/p>\n\n\n\n<figure class=\"wp-block-image aligncenter size-full\"><img decoding=\"async\" width=\"844\" height=\"378\" src=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/ARM-2.png\" alt=\"Screenshot of the &quot;DIGITAL INPUTS&quot; tab on the Fetura CLOUD platform. The screenshot shows the alarm arming confirmation panel, with the &quot;Arm Alarm&quot; confirmation button selected. \" class=\"wp-image-14402\" srcset=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/ARM-2.png 844w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/ARM-2-300x134.png 300w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/ARM-2-768x344.png 768w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/ARM-2-50x22.png 50w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/ARM-2-60x27.png 60w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/ARM-2-100x45.png 100w\" sizes=\"(max-width: 844px) 100vw, 844px\" \/><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\">Once the operation has been completed successfully, a confirmation message will appear (highlighted in blue), and the input status will be updated (highlighted in red).<\/p>\n\n\n\n<figure class=\"wp-block-image aligncenter size-large\"><img decoding=\"async\" width=\"1024\" height=\"287\" src=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/ARM-3-1024x287.png\" alt=\"A screenshot of the &quot;DIGITAL INPUTS&quot; tab on the Fetura CLOUD platform. The screenshot shows the IN1 input panel and the alarm arming confirmation panel. \" class=\"wp-image-14403\" srcset=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/ARM-3-1024x287.png 1024w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/ARM-3-300x84.png 300w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/ARM-3-768x215.png 768w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/ARM-3-50x14.png 50w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/ARM-3-60x17.png 60w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/ARM-3-100x28.png 100w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/ARM-3.png 1532w\" sizes=\"(max-width: 1024px) 100vw, 1024px\" \/><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\">Disarming the alarm is done in exactly the same way. The only difference is that you select the <strong>DISARM ALARM<\/strong> option. <\/p>\n\n\n\n<h2 class=\"wp-block-heading\">3. Alarm Configuration<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">This is the most important part of the configuration. Here, you specify when the alarm should be triggered, how quickly it should respond, and how it should be handled. <\/p>\n\n\n\n<p class=\"wp-block-paragraph\">To access the configuration, open the settings menu and select the <strong>ALARM CONFIGURATION<\/strong> option (highlighted in red).<\/p>\n\n\n\n<figure class=\"wp-block-image aligncenter size-large\"><img decoding=\"async\" width=\"1024\" height=\"524\" src=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-1-1024x524.png\" alt=\"Screenshot of the &quot;DIGITAL INPUTS&quot; tab on the Fetura CLOUD platform. The screenshot shows the digital input panels, with the tabs visible after clicking the three dots. The &quot;Alarm Configuration&quot; option is selected.  \" class=\"wp-image-14404\" srcset=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-1-1024x524.png 1024w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-1-300x153.png 300w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-1-768x393.png 768w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-1-50x26.png 50w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-1-1536x785.png 1536w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-1-60x31.png 60w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-1-100x51.png 100w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-1.png 1555w\" sizes=\"(max-width: 1024px) 100vw, 1024px\" \/><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\">When you open the configuration window, you&#8217;ll see the following items:<\/p>\n\n\n\n<ul class=\"wp-block-list\">\n<li><strong>Alarm trigger<\/strong> (highlighted in red),<\/li>\n\n\n\n<li><strong>Minimum signal duration<\/strong> (highlighted in blue),<\/li>\n\n\n\n<li><strong>Alarm delay<\/strong> (highlighted in green),<\/li>\n\n\n\n<li><strong>Alarm reset type<\/strong> (highlighted in orange),<\/li>\n\n\n\n<li><strong>Signal preview<\/strong> (highlighted in brown),<\/li>\n\n\n\n<li>The <strong>Cancel <\/strong>and <strong>Save<\/strong> Changes buttons (highlighted in gray).<\/li>\n<\/ul>\n\n\n\n<figure class=\"wp-block-image aligncenter size-large\"><img decoding=\"async\" width=\"1024\" height=\"702\" src=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-2-1024x702.png\" alt=\"Screenshot of the &quot;DIGITAL INPUTS&quot; tab on the Fetura CLOUD platform. The screenshot shows the alarm configuration panel, which includes:\nAlarm trigger (highlighted in red), \n\nMinimum signal duration (highlighted in blue),\n\nAlarm delay (highlighted in green),\n\nAlarm reset type (highlighted in orange),\n\nSignal preview (highlighted in brown),\n\nThe &quot;Cancel&quot; and &quot;Save Changes&quot; buttons (highlighted in gray).\" class=\"wp-image-14405\" srcset=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-2-1024x702.png 1024w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-2-300x206.png 300w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-2-768x526.png 768w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-2-50x34.png 50w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-2-60x41.png 60w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-2-100x69.png 100w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-2.png 1246w\" sizes=\"(max-width: 1024px) 100vw, 1024px\" \/><\/figure>\n\n\n\n<h3 class=\"wp-block-heading\">3.1. Alarm Trigger<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">The alarm trigger determines under what input conditions FarmWatch Pro should trigger an alarm.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">There are two states to choose from:<\/p>\n\n\n\n<ul class=\"wp-block-list\">\n<li><strong>Low state (0)<\/strong> \u2013 signal loss.<\/li>\n\n\n\n<li><strong>High state (1)<\/strong> \u2013 the signal is present.<\/li>\n<\/ul>\n\n\n\n<p class=\"wp-block-paragraph\">If you&#8217;re not sure which mode to select, check the operation of the connected device or its documentation.<\/p>\n\n\n\n<figure class=\"wp-block-image aligncenter size-full\"><img decoding=\"async\" width=\"296\" height=\"231\" src=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-3.png\" alt=\"The photo shows the &quot;Alarm Trigger&quot; section in the alarm configuration panel.\" class=\"wp-image-14406\" srcset=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-3.png 296w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-3-50x39.png 50w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-3-60x47.png 60w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-3-100x78.png 100w\" sizes=\"(max-width: 296px) 100vw, 296px\" \/><\/figure>\n\n\n\n<h4 class=\"wp-block-heading\">Example 1 \u2013 Checking the Device&#8217;s Operation<\/h4>\n\n\n\n<p class=\"wp-block-paragraph\">Let&#8217;s assume that a sensor is connected to FarmWatch Pro that continuously sends a signal during normal operation. The absence of a signal may indicate a device malfunction, a damaged cable, or a power outage. <\/p>\n\n\n\n<p class=\"wp-block-paragraph\">In this case, you should select <strong>the low state<\/strong> as the alarm trigger. This will ensure that the alarm is triggered when the signal disappears. <\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>Normal operation:<\/strong> signal is present \u2192 no alarm.<br><strong>Device failure or disconnection:<\/strong> signal disappears \u2192 alarm.<\/p>\n\n\n\n<h4 class=\"wp-block-heading\">Example 2 \u2013 Event Detection<\/h4>\n\n\n\n<p class=\"wp-block-paragraph\">Let&#8217;s assume that a motion sensor is connected. Under normal conditions, it does not send a signal; the signal is only triggered when motion is detected. <\/p>\n\n\n\n<p class=\"wp-block-paragraph\">In this case, select <strong>&#8220;High&#8221;<\/strong> as the alarm trigger. This will cause the alarm to be triggered when the sensor detects motion and sends a signal. <\/p>\n\n\n\n<p class=\"wp-block-paragraph\"><strong>No motion:<\/strong> no signal \u2192 no alarm.<br><strong>Motion detected:<\/strong> a signal is generated \u2192 alarm.<\/p>\n\n\n\n<h4 class=\"wp-block-heading\">How can I remember this?<\/h4>\n\n\n\n<p class=\"wp-block-paragraph\">If you want the alarm to trigger when <strong>the signal appears<\/strong>, select <strong>the high state<\/strong>.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">If you want the alarm to trigger when <strong>the signal disappears<\/strong>, select <strong>the low state<\/strong>.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\">3.2. Minimum signal duration<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">The minimum signal duration specifies how long an alarm condition must persist at an input for FarmWatch Pro to recognize it as a genuine problem and trigger an alarm. This helps prevent alarms caused by brief disturbances or temporary changes in the input status. <\/p>\n\n\n\n<p class=\"wp-block-ht-blocks-messages wp-block-hb-message wp-block-hb-message--withicon is-style-info\">You can adjust the time using the slider or the \u201c+\u201d and \u201c-\u201d buttons.<br><strong>Setting range:<\/strong> 0 seconds to 10 minutes.<br>A single click of the \u201c+\u201d or \u201c-\u201d button changes the value by 0.1 seconds.<\/p>\n\n\n\n<figure class=\"wp-block-image aligncenter size-full\"><img decoding=\"async\" width=\"885\" height=\"157\" src=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-4.png\" alt=\"The photo shows the &quot;Minimum Signal Duration&quot; section in the alarm configuration panel.\" class=\"wp-image-14407\" srcset=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-4.png 885w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-4-300x53.png 300w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-4-768x136.png 768w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-4-50x9.png 50w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-4-60x11.png 60w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-4-100x18.png 100w\" sizes=\"(max-width: 885px) 100vw, 885px\" \/><\/figure>\n\n\n\n<p class=\"wp-block-ht-blocks-messages wp-block-hb-message wp-block-hb-message--withicon is-style-alert\">For most applications involving climate controllers, power outages, and device monitoring, we recommend setting the value to <strong>1 minute<\/strong>.<br>This ensures that the system will not respond to brief signal interruptions, which typically do not require intervention.<br>A time setting that is too short may result in a large number of unnecessary alarms and faster depletion of the notification quota.<\/p>\n\n\n\n<h4 class=\"wp-block-heading\">Example<\/h4>\n\n\n\n<p class=\"wp-block-paragraph\">A climate controller is connected to FarmWatch Pro. As a result of a momentary power outage, the device stops transmitting a signal. If the minimum signal duration is set to 1 minute:  <\/p>\n\n\n\n<ul class=\"wp-block-list\">\n<li>If the signal returns after a few seconds, it will not trigger an alarm,<\/li>\n\n\n\n<li>If there is no signal for more than a minute, an alarm will be triggered.<\/li>\n<\/ul>\n\n\n\n<h3 class=\"wp-block-heading\">3.3. Delay in reporting an alarm<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">The alarm delay specifies how long the system should wait before sending a notification after an alarm is detected.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">The alarm will be detected immediately, but an SMS, phone call, or in-app notification will not be sent until the set time has elapsed.<\/p>\n\n\n\n<p class=\"wp-block-ht-blocks-messages wp-block-hb-message wp-block-hb-message--withicon is-style-info\">You can adjust the time using the slider or the \u201c+\u201d and \u201c-\u201d buttons.<br><strong>Setting range:<\/strong> 0 seconds to 10 minutes.<br>A single click of the \u201c+\u201d or \u201c-\u201d button changes the value by 0.1 seconds.<\/p>\n\n\n\n<figure class=\"wp-block-image aligncenter size-full\"><img decoding=\"async\" width=\"1172\" height=\"150\" src=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-5.png\" alt=\"The photo shows the &quot;Alarm Delay&quot; section in the alarm configuration panel.\" class=\"wp-image-14408\" srcset=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-5.png 1172w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-5-300x38.png 300w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-5-1024x131.png 1024w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-5-768x98.png 768w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-5-50x6.png 50w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-5-60x8.png 60w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-5-100x13.png 100w\" sizes=\"(max-width: 1172px) 100vw, 1172px\" \/><\/figure>\n\n\n\n<h4 class=\"wp-block-heading\">What is the purpose of the delay?<\/h4>\n\n\n\n<p class=\"wp-block-paragraph\">The delay gives the user time to respond before the notification is sent.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">It is particularly useful in alarm systems, where authorized personnel can enter the premises and disarm the alarm before a notification is sent.<\/p>\n\n\n\n<p class=\"wp-block-ht-blocks-messages wp-block-hb-message wp-block-hb-message--withicon is-style-alert\">For alarms triggered by motion sensors, we recommend setting the delay to at least <strong>2 minutes<\/strong>.<\/p>\n\n\n\n<h4 class=\"wp-block-heading\">Example:<\/h4>\n\n\n\n<p class=\"wp-block-paragraph\">Motion sensors and an alarm disarm panel were installed on the farm. When motion is detected, a countdown begins.   <\/p>\n\n\n\n<ul class=\"wp-block-list\">\n<li>If an employee disarms the alarm before the set time has elapsed, no notification will be sent.<\/li>\n\n\n\n<li>If the alarm is not disarmed, the system will send a notification about the detected event.<\/li>\n<\/ul>\n\n\n\n<h3 class=\"wp-block-heading\">3.4. Manual\/Automatic Alarm Reset<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">When an alarm is triggered, the system can clear it in two ways.<\/p>\n\n\n\n<h4 class=\"wp-block-heading\">Manual Alarm Reset<\/h4>\n\n\n\n<p class=\"wp-block-paragraph\">Once an alarm is triggered, it remains active until the user manually clears it. Even if the cause of the alarm no longer exists, the alarm will still be displayed as active. <\/p>\n\n\n\n<figure class=\"wp-block-image size-full\"><img decoding=\"async\" width=\"1172\" height=\"197\" src=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-6.1.png\" alt=\"The photo shows the &quot;Alarm Clear Type&quot; section in the alarm configuration panel, with the &quot;Manual Clear&quot; option selected.\" class=\"wp-image-14409\" srcset=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-6.1.png 1172w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-6.1-300x50.png 300w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-6.1-1024x172.png 1024w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-6.1-768x129.png 768w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-6.1-50x8.png 50w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-6.1-60x10.png 60w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-6.1-100x17.png 100w\" sizes=\"(max-width: 1172px) 100vw, 1172px\" \/><\/figure>\n\n\n\n<h4 class=\"wp-block-heading\">When is it best to choose manual cleaning?<\/h4>\n\n\n\n<p class=\"wp-block-paragraph\">This option works best in security systems where a single event notification is sufficient.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\">Example<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">A motion sensor is connected to the system. When a person is detected, an alarm is triggered and remains active until it is manually deactivated. This ensures that the user does not miss any information about a possible intrusion onto the premises.  <\/p>\n\n\n\n<h4 class=\"wp-block-heading\">Automatic Alarm Cleaning<\/h4>\n\n\n\n<p class=\"wp-block-paragraph\">Once the cause of the alarm has been resolved, the system will automatically clear the alarm. If the problem occurs again, a new alarm will be triggered. <\/p>\n\n\n\n<figure class=\"wp-block-image size-full\"><img decoding=\"async\" width=\"1175\" height=\"201\" src=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-6.2.png\" alt=\"The photo shows the &quot;Alarm Clear Type&quot; section in the alarm configuration panel, with the &quot;Automatic Clear&quot; option selected.\" class=\"wp-image-14410\" srcset=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-6.2.png 1175w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-6.2-300x51.png 300w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-6.2-1024x175.png 1024w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-6.2-768x131.png 768w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-6.2-50x9.png 50w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-6.2-60x10.png 60w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-6.2-100x17.png 100w\" sizes=\"(max-width: 1175px) 100vw, 1175px\" \/><\/figure>\n\n\n\n<h4 class=\"wp-block-heading\">When should you choose automatic cleaning?<\/h4>\n\n\n\n<p class=\"wp-block-paragraph\">This option works best for monitoring environmental parameters and device operation.<\/p>\n\n\n\n<h3 class=\"wp-block-heading\">Example<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">FarmWatch Pro monitors the temperature inside the building. If the temperature exceeds the threshold, the system triggers an alarm. Once the temperature returns to normal, the alarm is automatically cleared. If the temperature later exceeds the threshold again, another alarm will be triggered.   <\/p>\n\n\n\n<h3 class=\"wp-block-heading\">3.5. Signal Preview<\/h3>\n\n\n\n<p class=\"wp-block-paragraph\">When you click the <strong>SHOW SIGNAL<\/strong> button, the signal waveform at the digital input will be displayed.  <\/p>\n\n\n\n<figure class=\"wp-block-image aligncenter size-full\"><img decoding=\"async\" width=\"413\" height=\"99\" src=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-7.1.png\" alt=\"The photo shows the &quot;Show Signal&quot; section in the alarm configuration panel.\" class=\"wp-image-14411\" srcset=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-7.1.png 413w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-7.1-300x72.png 300w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-7.1-50x12.png 50w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-7.1-60x14.png 60w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-7.1-100x24.png 100w\" sizes=\"(max-width: 413px) 100vw, 413px\" \/><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\">Here you can check:<\/p>\n\n\n\n<ul class=\"wp-block-list\">\n<li>current status of the entrance,<\/li>\n\n\n\n<li>signal history,<\/li>\n\n\n\n<li>times when alarms occurred,<\/li>\n\n\n\n<li>current alarm status.<\/li>\n<\/ul>\n\n\n\n<figure class=\"wp-block-image aligncenter size-full\"><img decoding=\"async\" width=\"387\" height=\"357\" src=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-7.2.png\" alt=\"The photo shows the &quot;Show Signal&quot; section open in the alarm configuration panel; &quot;Show Signal&quot; has been changed to &quot;Hide Signal.&quot; The signal waveform is visible in low mode, with the caption \u201cSignal Read\u201d above the waveform. \" class=\"wp-image-14412\" srcset=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-7.2.png 387w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-7.2-300x277.png 300w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-7.2-50x46.png 50w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-7.2-60x55.png 60w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/AC-7.2-100x92.png 100w\" sizes=\"(max-width: 387px) 100vw, 387px\" \/><\/figure>\n\n\n\n<h2 class=\"wp-block-heading\">4. Alarm Schedule<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">The schedule allows you to automatically arm and disarm the alarm at specific times. To access the schedule, open the settings menu and select the <strong>SCHEDULE<\/strong> option (highlighted in red). <\/p>\n\n\n\n<figure class=\"wp-block-image size-large\"><img decoding=\"async\" width=\"1024\" height=\"516\" src=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/S-1-1024x516.png\" alt=\"Screenshot of the &quot;DIGITAL INPUTS&quot; tab on the Fetura CLOUD platform. The screenshot shows the digital input panels, with the tabs visible after clicking the three dots. The &quot;Schedule&quot; option is selected.  \" class=\"wp-image-14413\" srcset=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/S-1-1024x516.png 1024w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/S-1-300x151.png 300w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/S-1-768x387.png 768w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/S-1-50x25.png 50w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/S-1-1536x774.png 1536w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/S-1-60x30.png 60w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/S-1-100x50.png 100w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/S-1.png 1547w\" sizes=\"(max-width: 1024px) 100vw, 1024px\" \/><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\">When you open the window, you&#8217;ll see the following settings:<\/p>\n\n\n\n<ul class=\"wp-block-list\">\n<li>automatic arming of the alarm (highlighted in red),<\/li>\n\n\n\n<li>automatic alarm disarm (highlighted in blue).<\/li>\n<\/ul>\n\n\n\n<p class=\"wp-block-paragraph\">Each section has a switch to turn the function on and controls for setting the time.<\/p>\n\n\n\n<p class=\"wp-block-ht-blocks-messages wp-block-hb-message wp-block-hb-message--withicon is-style-info\"><strong>Setting range:<\/strong> 00:00 to 23:59.<br>A single click on the \u201c+\u201d or \u201c-\u201d button changes the time by 1 minute.<\/p>\n\n\n\n<figure class=\"wp-block-image aligncenter size-full\"><img decoding=\"async\" width=\"806\" height=\"741\" src=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/S-2.png\" alt=\"A screenshot of the &quot;DIGITAL INPUTS&quot; tab on the Fetura CLOUD platform. The screenshot shows the schedule confirmation panel, with the automatic arming and automatic disarming sections highlighted. Both sections have a toggle switch to enable the feature (they are turned off in the screenshot) and a slider with \u201c+\u201d and \u201c-\u201d buttons on either side. Above the &quot;+&quot; symbol, you can see the set time (in the screenshot, the time is 00:00, and the slider ball is set all the way to the left). At the very bottom are the CLOSE and SAVE buttons (Close is gray, and Save is green).    \" class=\"wp-image-14414\" srcset=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/S-2.png 806w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/S-2-300x276.png 300w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/S-2-768x706.png 768w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/S-2-50x46.png 50w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/S-2-60x55.png 60w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/S-2-100x92.png 100w\" sizes=\"(max-width: 806px) 100vw, 806px\" \/><\/figure>\n\n\n\n<h4 class=\"wp-block-heading\">Example:<\/h4>\n\n\n\n<p class=\"wp-block-paragraph\">At the farm, employees are on the premises from 8:00 a.m. to 4:00 p.m. The alarm should only be active outside of working hours. In this case, you can set:  <\/p>\n\n\n\n<ul class=\"wp-block-list\">\n<li>automatic arming of the alarm at 4:00 p.m.,<\/li>\n\n\n\n<li>The alarm is automatically disarmed at 8:00 a.m.<\/li>\n<\/ul>\n\n\n\n<p class=\"wp-block-paragraph\">As a result, the alarm will be active only when there should be no employees on the premises.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">5. Name Change<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">To rename a digital input, go to Settings (highlighted in red), then select <strong>FarmWatch Pro<\/strong> (highlighted in blue), and go to Digital Input Management (highlighted in green).<\/p>\n\n\n\n<figure class=\"wp-block-image size-large\"><img decoding=\"async\" width=\"1024\" height=\"465\" src=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/N-1-1024x465.png\" alt=\"A screenshot of the settings panel on the Fetura CLOUD platform. The screenshot highlights the icon labeled &quot;Settings&quot; on the side navigation bar. In the &quot;Settings&quot; section, there is a vertical navigation bar to the right of the main bar with the &quot;FarmWatch Pro&quot; tab highlighted. This section contains three options: \u201cFarmWatch Pro Management,\u201d \u201cTemperature Sensor Management (FarmWatch Pro),\u201d and \u201cDigital Input Management (FarmWatch Pro).\u201d The last option is selected.    \" class=\"wp-image-14415\" srcset=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/N-1-1024x465.png 1024w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/N-1-300x136.png 300w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/N-1-768x349.png 768w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/N-1-50x23.png 50w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/N-1-1536x698.png 1536w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/N-1-60x27.png 60w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/N-1-100x45.png 100w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/N-1.png 1866w\" sizes=\"(max-width: 1024px) 100vw, 1024px\" \/><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\">Select the desired input (highlighted in red), and then click the arrow (highlighted in blue).<\/p>\n\n\n\n<figure class=\"wp-block-image size-large\"><img decoding=\"async\" width=\"1024\" height=\"766\" src=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/N-2-1024x766.png\" alt=\"Screenshot of the digital input management interface on the Fetura CLOUD platform. The screenshot shows the digital input management panel. The entire interface is presented in a table with the following formatting:\ncheckbox; Sequence number); Input number (IN1-IN8); FarmWatch name; Input name. At the very bottom, outside the table, there is information about the number of selected inputs and an arrow to navigate to the settings.   \" class=\"wp-image-14416\" srcset=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/N-2-1024x766.png 1024w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/N-2-300x224.png 300w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/N-2-768x575.png 768w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/N-2-50x37.png 50w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/N-2-60x45.png 60w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/N-2-100x75.png 100w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/N-2.png 1171w\" sizes=\"(max-width: 1024px) 100vw, 1024px\" \/><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\">Enter the new name in the edit field (highlighted in red) and save your changes by clicking the save button (highlighted in blue).<\/p>\n\n\n\n<figure class=\"wp-block-image size-full\"><img decoding=\"async\" width=\"781\" height=\"376\" src=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/N-3.png\" alt=\"A screenshot of the digital input configuration on the Fetura CLOUD platform. The screenshot shows the digital input configuration tab, where the renaming panel is visible. The panel is labeled &quot;General&quot; (top-left corner of the panel). In the center-left is \u201cDevice Name,\u201d with a text field below it for entering a name. In the upper-right corner is a save icon highlighted in green.    \" class=\"wp-image-14417\" srcset=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/N-3.png 781w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/N-3-300x144.png 300w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/N-3-768x370.png 768w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/N-3-50x24.png 50w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/N-3-60x29.png 60w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/N-3-100x48.png 100w\" sizes=\"(max-width: 781px) 100vw, 781px\" \/><\/figure>\n\n\n\n<p class=\"wp-block-ht-blocks-messages wp-block-hb-message wp-block-hb-message--withicon is-style-alert\">It&#8217;s a good idea to give inputs names that clearly describe their function and where they are supposed to be located.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\">6. Historical Data<\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">To view the event history for the selected input, click the arrow next to the input (highlighted in red).<\/p>\n\n\n\n<figure class=\"wp-block-image size-large\"><img decoding=\"async\" width=\"1024\" height=\"163\" src=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/H-1-1024x163.png\" alt=\"Screenshot of the &quot;DIGITAL INPUTS&quot; tab on the Fetura CLOUD platform. The screenshot shows the IN1 input panel with a downward-pointing arrow highlighted on the right. \" class=\"wp-image-14418\" srcset=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/H-1-1024x163.png 1024w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/H-1-300x48.png 300w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/H-1-768x122.png 768w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/H-1-50x8.png 50w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/H-1-60x10.png 60w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/H-1-100x16.png 100w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/H-1.png 1530w\" sizes=\"(max-width: 1024px) 100vw, 1024px\" \/><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\">In the history panel, you&#8217;ll find:<\/p>\n\n\n\n<ul class=\"wp-block-list\">\n<li>selection of the date range (highlighted in red),<\/li>\n\n\n\n<li>data freshness status and refresh button (highlighted in blue),<\/li>\n\n\n\n<li>export data to an Excel file (highlighted in green),<\/li>\n\n\n\n<li>a list of events, including the date, time, and event type (highlighted in orange),<\/li>\n\n\n\n<li>page navigation buttons (highlighted in brown),<\/li>\n\n\n\n<li>Selecting the number of events to display on the page (highlighted in gray).<\/li>\n<\/ul>\n\n\n\n<figure class=\"wp-block-image size-large\"><img decoding=\"async\" width=\"1024\" height=\"483\" src=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/H-2-1024x483.png\" alt=\"A screenshot of the &quot;DIGITAL INPUTS&quot; tab on the Fetura CLOUD platform. The screenshot shows the IN1 input panel with the input event history panel expanded after clicking the arrow on the right side of the input panel. The history panel displays:\ndate range selection (highlighted in red),  \n\ndata freshness status and refresh button (highlighted in blue),\n\nexport data to an Excel file (highlighted in green),\n\na list of events, including the date, time, and event type (highlighted in orange),\n\npage navigation buttons (highlighted in brown),\n\nSelecting the number of events to display on the page (highlighted in gray).\" class=\"wp-image-14419\" srcset=\"https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/H-2-1024x483.png 1024w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/H-2-300x142.png 300w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/H-2-768x363.png 768w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/H-2-50x24.png 50w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/H-2-1536x725.png 1536w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/H-2-60x28.png 60w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/H-2-100x47.png 100w, https:\/\/help.fetura.pl\/wp-content\/uploads\/2026\/07\/H-2.png 1559w\" sizes=\"(max-width: 1024px) 100vw, 1024px\" \/><\/figure>\n\n\n\n<p class=\"wp-block-paragraph\">Historical data allows you to track all changes in the input status and determine when and why an alarm was triggered.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">We hope this article has helped you set up alarms on the FarmWatch Pro digital inputs. If you encounter any issues, we encourage you to check out the other articles in the Fetura CLOUD knowledge base. <\/p>\n\n\n<!-- fetura-ai-tags: category=CLIMATE_CONTROLLER; type=procedure; keywords=configure digital input alarms FarmWatch, arm disarm alarm FarmWatch CLOUD, alarm trigger high low state, minimum signal duration alarm, alarm delay notification, manual automatic alarm reset, alarm schedule FarmWatch; synonyms=digital input configuration, sensor arm and disarm, notification delay setting, signal debounce time, alarm scheduling -->","protected":false},"excerpt":{"rendered":"<p>This article will guide you step by step through the process of configuring alarms for digital inputs in the FarmWatch Pro system using the Fetura CLOUD platform. 1. Preview To view the digital inputs, go to the Dashboard section (highlighted in red). Next, click the three-dot icon in the top&#8230;<\/p>\n","protected":false},"author":28,"comment_status":"open","ping_status":"closed","template":"","format":"standard","meta":{"footnotes":""},"ht-kb-category":[111],"ht-kb-tag":[],"class_list":["post-14109","ht_kb","type-ht_kb","status-publish","format-standard","hentry","ht_kb_category-farmwatch-pro-en"],"_links":{"self":[{"href":"https:\/\/help.fetura.pl\/en\/wp-json\/wp\/v2\/ht-kb\/14109","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/help.fetura.pl\/en\/wp-json\/wp\/v2\/ht-kb"}],"about":[{"href":"https:\/\/help.fetura.pl\/en\/wp-json\/wp\/v2\/types\/ht_kb"}],"author":[{"embeddable":true,"href":"https:\/\/help.fetura.pl\/en\/wp-json\/wp\/v2\/users\/28"}],"replies":[{"embeddable":true,"href":"https:\/\/help.fetura.pl\/en\/wp-json\/wp\/v2\/comments?post=14109"}],"version-history":[{"count":11,"href":"https:\/\/help.fetura.pl\/en\/wp-json\/wp\/v2\/ht-kb\/14109\/revisions"}],"predecessor-version":[{"id":14635,"href":"https:\/\/help.fetura.pl\/en\/wp-json\/wp\/v2\/ht-kb\/14109\/revisions\/14635"}],"wp:attachment":[{"href":"https:\/\/help.fetura.pl\/en\/wp-json\/wp\/v2\/media?parent=14109"}],"wp:term":[{"taxonomy":"ht_kb_category","embeddable":true,"href":"https:\/\/help.fetura.pl\/en\/wp-json\/wp\/v2\/ht-kb-category?post=14109"},{"taxonomy":"ht_kb_tag","embeddable":true,"href":"https:\/\/help.fetura.pl\/en\/wp-json\/wp\/v2\/ht-kb-tag?post=14109"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}